Description
The Fluke 1670 Series Multifunction Installation Testers will revolutionize the way you work. With an ergonomic design, seamless user interface, integrated data management capabilities, wireless connectivity (1673 FC and 1674 FC), and comprehensive reporting software, the 1670 Series sets the new standard for an integrated installation testing solution. Reliable installation testing is essential for ensuring the safety, optimal functionality, and integrity of a facility’s electrical systems. The 1670 Series’ rugged design allows you to verify the safety of electrical installations in domestic, commercial, and industrial applications while meeting the requirements of IEC/HD 60364-6 and all relevant local installation test standards. With the 1670 Series, you’ll be able to perform your required testing faster and reduce the time you spend on documentation, all while having the ultimate confidence in the data you’re collecting.
Includes:
- 1 x Multifunction installation tester
- 1 x Heavy duty mains cord with single input connector
- 1 x Hard case
- 1 x USB-C Power adapter for charging
- 1 x Remote control probe
- 1 x Hanging strap
- 1 x Zero adapter
- 3 x Test leads and probes
- 3 x Alligator clips
- 1 x Li-Ion battery
Features:
- Simple bidirectional user interface eliminates complex multi-level menus
- Easy setup with the full-color touch screen, smart device, or a PC
- Fast, accurate testing with Auto Test and Automatic Measurement Validation
- Fluke Connect compatibility eliminates tedious data entry
- Preview results and generate certificates on site with Fluke TruTest™️ software
Specifications:
- Range: 600V
- Resolution: 0.1 V
- Accuracy 45 Hz – 66 Hz: 0.8% + 3
- Input impedance: 320 kΩ
- Overload protection: 660 V
- Continuity testing (RLO)
- Range (autoranging): 20 Ω / 200 Ω / 2000 Ω
- Resolution: 0.01 Ω / 0.1 Ω / 1 Ω
- Open Circuit Voltage: >4V
- Insulation resistance measurement (RISO)
- Accuracy of Test voltage (at rated test current): +10%, -0%
- Test voltage:
- 100 V
- 250 V
- 500 V
- 1000 V
- Insulation resistance range:
- 10 MΩ / 50 MΩ
- 20 MΩ / 100 MΩ
- 20 MΩ / 200 MΩ
- 20 MΩ / 200 MΩ / 500 MΩ
- 100 MΩ / 200 MΩ / 1000 MΩ
- Resolution:
- 0.01 MΩ / 0.1 MΩ
- 0.01 MΩ / 0.1 MΩ
- 0.01 MΩ / 0.1 MΩ
- 0.01 MΩ / 0.1 MΩ / 1 MΩ
- 0.01 MΩ / 0.1 MΩ / 1 MΩ
- Test current:
- 1 mA @ 50 kΩ
- 1 mA @ 100 kΩ
- 1 mA @ 250 kΩ
- 1 mA @ 500 kΩ
- 1 mA @ 1 MΩ
- Loop and line impedance (ZI)
- Range: 10 Ω / 0.001 Ω / High current mΩ mode
- Resolution: 0.01 Ω / 0.1 Ω / 1 Ω
- Prospective earth fault current, PSC test
- Range: 2000 A / 10 kA (50 kA)
- Resolution: 1 A / 0.1 kA
- Computation: Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
- RCD testing, RCD types tested
- RCD Type:
- A4, AC¹, G², S³
- Notes:
- ¹Responds to AC
- ²General, no delay
- ³Time delay
- 4Responds to pulsed signal
- 5Responds to smooth DC signal
- Tripping speed test (ΔT)
- Current settings¹:
- 10-30-100-300-500-1000 mA – VAR
- 10-30-100 mA
- Multiplier: x ½, x 1, x 5
- Measurement range:
- RCD Type G:
- 310 ms
- 50 ms
- RCD Type S:
- 510 ms
- 160 ms
- Specified trip current ranges (EN 61008-1): 50% to 100% for Type AC, 35% to 140% for Type A (>10 mA), 35% to 200% for Type A (≤10 mA), 50% to 200% for Type B, ²5% for Type B
- Battery size: Type AA, 6 ea.
- Sealing: IP-40
- Safety: Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition
- Overvoltage: CAT III / 500V; CAT IV 300V
- Performance: EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition
- Size (L x W x H): 262.5mm x 141.9mm x 119.3 mm
- Weight: 1.6kg

Reviews